Three-phase, transformerless, UPS range is designed for computer rooms, data centres, precision instruments, auto manufacturing and industrial processes. The Kohler EW 6000 range is available from 10-600kVA.

Description

The Kohler EW 6000, transformerless, standalone UPS range includes three key products:

  • 10-120kVA
  • 160-200kVA
  • 300-600kVA

The smaller size of the range is designed toward supporting finance companies; medical equipment and telecommunication systems, whilst the larger sized UPS are designed more for larger data centres, auto manufacturing and industrial processes.

The Kohler EW 6000 range combines high reliability with high quality performance, with enhanced green factors such as ECO mode. The flexibility and user-friendliness of the design, alongside advanced technology, provides an outstanding solution for your UPS requirements.

To compare the three key product ranges, click on the Technical Specification tab.

Complete the ‘Get a Quote’ enquiry or ring us directly on +65 6302 0702 and we’ll get back to you immediately to discuss your requirements.

 

Additional information

Actual kVA

10-600 kVA

Standalone / Modular

Standalone

Type

Three Phase EW

Technical Specification

Below are the specifications and available configurations for the Kohler EW 6000, transformerless, UPS range.

Input Specifications

ModelEW 6000
(UPS 10-120kVA)
EW 6000
(UPS 160-200kVA)
EW 6000
(UPS 300-600kVA)
Nominal Voltage (Vac)380/400/415 (138~485 L L)380/400/415 (L L)380/400/415
TypeThree phaseThree phaseThree phase
Standalone/ModularStandaloneStandaloneStandalone
TransformerlessYesYesYes
Power Factor (PF)>0.990.990.99
THDi<1% at linear<3%<3%
Input Voltage (Vac)380/400/415 (138~485 L L)380/400/415 (L L)380/400/415
Input Frequency (Hz)40~7050/60+10%50/60
Bypass Voltage Range (Vac)380/400/415: -20%~+15%380/400/415:
-20%~+15%
380/400/415:
-25%~+20%

Output Specifications

ModelEW 6000
(UPS 10-120kVA)
EW 6000
(UPS 160-200kVA)
EW 6000
(UPS 300-600kVA)
Output Capacity (kVA)10, 20, 30, 40, 50, 60, 80, 100, 120160, 200300, 400, 500, 600
Output Voltage (Vac)L-N: 220/230/240+1%
L-L: 380/400/415+1%
380/400/415+1%380/400/415+1%
WaveformPure sine wave
THD <1% (at linear)
Pure sine wave
THD <1% (100% linear load)
THD <0.5% (linear load)
<5% (non-linear load)
System Efficiency>95%>=95%Up to 97%
Output Overload Capacity105-115% for 60 minutes,
116-130% for 10 minutes,
131-150% for 1 minute,
Above 150% for 200ms
105%~115% for 60 mins, 116%~130% for 10 mins, 131%~150% for 1 min, above 150% for 200msUp to 130% load for 10 minutes,
Up to 150% for 1 minute

Battery Specifications

ModelEW 6000
(UPS 10-120kVA)
EW 6000
(UPS 160-200kVA)
EW 6000
(UPS 300-600kVA)
Battery Voltage (VDC)+192
(+180/ +204/ +216/ +228/ +240
settable for long backup type)
480
(32-40 selectable)
480
(12V battery from 32-44 selectable)
Battery Charging Current (A)1-10 settable (up to 40kVA)
1-20 settable (50-100kVA)
1-30 settable (>100kVA)
1-40 settable (160kVA) / 1-50 settable (200kVA)20-100

Other

ModelEW 6000
(UPS 10-120kVA)
EW 6000
(UPS 160-200kVA)
EW 6000
(UPS 300-600kVA)
DisplayTouchscreen + LEDTouchscreen + LEDTouchscreen + LED
Communication InterfaceRS485 MODBUS
Dry Contact
(SNMP adapter optional)
RS232/485 MODBUS
Dry Contact
(SNMP optional)
RS485 MODBUS
Dry Contact
(SNMP optional)
Noise (dB)<65<75<75
Working Temperature (°C)0~+40-5~+40
Dimensions (mm)
WxDxH
up to:
450 x 840 x 1400
600 x 900 x 16001600 x 800 x 1800
Max Weight (kg)120-350320-350950-1300

Documentation

Brochure

Download Kohler EW 6000 Range (UPS 10-600kVA) Brochure

Technical Specification

 Download Kohler EW 6000 (10-120kVA) Technical Specification
Download Kohler EW 6000 (160-200kVA) Technical Specification
 Download Kohler EW 6000 (300-600kVA) Technical Specification